FUJITSU

PRODUCT | VRF SYSTEM | V-II SERIES

Rating Capacity range 32HP

AJY288LALHH

Outdoor units

Space Saving Combination

Unit 1 Unit 2 Unit 3
AJY108LALH AJY108LALH AJYA72LALH

Space Saving Combination

Features

Efficiency in actual operation

  • Space saving combination
  • Energy efficiency combination
  • Space saving and compact size
  • Energy saving technology that boosted operation efficiency

Design Flexibility

  • Overall piping length 1,000m
  • High static pressure of 80Pa

More Comfort

  • Non-stop oil recovery operation

Easy Service & Maintenance

  • Indoor unit continuous operation

 

Specifications

Rating Capacity range 32HP
Set Model name AJY288LALHH
Units AJY108LALH   AJY108LALH   AJYA72LALH
Maximum Connectable Indoor Unit*1 48
Indoor unit connectable capacity 44.7 - 134.1kW
Power source 3-phase 4 wire, 400 V, 50Hz
Capacity Cooling  89.4kW  Heating 100.0kW
Input power Cooling  24.75kW  Heating 24.28kW
EER Cooling  3.61W/W
COP Heating  4.12W/W
Air flow late 11,100m³/h × 3
Sound pressure level*2 Cooling  62dB(A)  Heating 64dB(A)
Maximum external static pressure 80Pa
Compresor motor output 3.9kW × 3 + 4.5kW × 2
Heat exchanger fin Blue fin
Dimensions 1,690(H) × 930(W) × 765(D)mm
1,690(H) × 930(W) × 765(D)mm
1,690(H) × 930(W) × 765(D)mm
Weight 275kg + 275kg + 220kg
Refrigerant charge 11.8kg × 2 + 11.2kg
Connection pipe diameter Liquid 19.05mm
Gas 34.92mm
Operation range Cooling  -5 to 46°CDB
Heating -20 to 21°CDB
  • *1Minimum connectable indoor unit number is 2.
    However ARXC72 and ARXC90 can be used signal connection.
  • *2The noise value is the value when measured in an anechoic room.
    When measured in the actual installed state, surrounding noise and reflections are received and the measured value is usually larger than the indicated value.
  • Note : Specifications are based on the following conditions.
  • Cooling : Indoor temperature of 27°CDB / 19°C, and outdoor temperature of 35°CDB / 24°C.
  • Heating : Indoor temperature of 20°CDB / (15°C), and outdoor temperature of 7°CDB / 6°C.
  • Pipe length : 7.5 m; Height difference between outdoor unit and indoor unit : 0 m.
    When cooling operation will be conducted at outdoor air temperature below -5°C, the outdoor unit must be installed in a position that is higher than or equal to those of indoor units.

Dimensions

AJY108LALH / AJYA72LALH

Outdoor Dimensions : 1,690(H) × 930(W) × 765(D)mm

A-Front side knockout position. B-Left side knockout position. C-Bottom side knockout position.


 