FUJITSU

PRODUCT | VRF SYSTEM | V-II TROPICAL SERIES

Rating Capacity range 34HP

AJY306LNLAH

Outdoor units

Space Saving Combination

Unit 1 Unit 2 Unit 3
AJY126LNLAH AJY090LNLAH AJY090LNLAH

Features

High ambient operation design

  • Possible to operate cooling up to 52ÂșC outdoor temperature.

Powerful cooling capacity design

  • Keeping high cooling power at even high ambient temperature.

Anti-corrosion treatment design

  • All metalic and PCB components are protected against corrosion.

 

Specifications

Rating Capacity range 34HP
Set Model name AJY306LNLAH
Units AJY126LNLAH   AJY090LNLAH   AJY090LNLAH
Maximum Connectable Indoor Unit*1 41
Indoor unit connectable capacity 48.0 - 124.8kW
Power source 3N ~ 400 V, 50Hz
Capacity Cooling (T1)  96.0kW  Cooling (T3)  79.3kW  Heating(T1) 108.0kW
Input power Cooling(T1)  26.99kW  Heating 27.11kW
EER Cooling(T1)  3.56W/W
COP Heating  3.98W/W
Air flow late 13,000m³/h + 11,100m³/hx 2
Sound pressure level*2 Cooling  64dB(A)  Heating 65dB(A)
Maximum external static pressure 80Pa
Compresor motor output 3.9kW x 3 + 45kW
Heat exchanger fin Blue fin
Dimensions 1,690(H) × 1,240 + 930 x 2(W) × 765(D)mm
Weight 303kg + 220kg + 220kg
Refrigerant charge 11.8 + 11.2 x 2
Connection pipe diameter Liquid 19.05mm
Gas 34.92mm
Operation range Cooling  -5 to 52°CDB*1
Heating -20 to 21°CDB
  • *1Minimum connectable indoor unit number is 2.
    However ARXC72 and ARXC90 can be used signal connection.
  • *2The noise value is the value when measured in an anechoic room.
    When measured in the actual installed state, surrounding noise and reflections are received and the measured value is usually larger than the indicated value.
  • Note : Specifications are based on the following conditions.
  • Cooling : Indoor temperature of 27°CDB / 19°C, and outdoor temperature of 35°CDB / 24°C.
  • Heating : Indoor temperature of 20°CDB / (15°C), and outdoor temperature of 7°CDB / 6°C.
  • Pipe length : 7.5 m; Height difference between outdoor unit and indoor unit : 0 m.
    When cooling operation will be conducted at outdoor air temperature below -5°C, the outdoor unit must be installed in a position that is higher than or equal to those of indoor units.

Dimensions

AJY126LNLAH

Outdoor Dimensions : 1,690(H) × 930(W) × 765(D)mm

AJY090LNLAH

Outdoor Dimensions : 1,690(H) × 930(W) × 765(D)mm

A-Front side knockout position. B-Left side knockout position. C-Bottom side knockout position.


 

Top of Page


ribbon